Trane · General · Heating

Heating test

XR203

What happens, in order

  1. Press the System button to select Heat.
  2. For heat pumps with a standing pilot auxiliary, light the pilot.
  3. Set the thermostat 1 degree above room temperature. The heating system should start and Heat On shows.
  4. For heat pumps with auxiliary, set 3 degrees above room temperature. Auxiliary heat should start and Heat On Aux shows.
  5. Set the thermostat 1 degree below room temperature. Heating should stop and the Heat On icon clears.

Codes you may see during this

Starting Soon

Applies to: XR203 thermostat

Models

TCONT203

More Trane general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR203 installation and user guide, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.