Trane · General · Cooling
Compressor optimization fan delay
What happens, in order
- On compressor start for a cool or heat pump heat call, the fan waits before starting so air is conditioned first.
- When the cool call ends and the compressor stops, the fan keeps running to capture more cooling.
- With CO set to OFF, there is no fan delay.
Timings and thresholds
| Item | Value |
|---|---|
| Fan start delay on compressor start | 5 seconds |
| Fan run-on after cool call ends | 20 seconds |
Applies to: Compressor optimization (screen 22) set On
Models
More Trane general sequences
- Energy management recovery (early start) · Heating
- Heating system test · Heating
- Heating test · Heating
- Compressor lockout delay · Cooling
- Cool Savings temperature offset · Cooling
- Cooling system test · Cooling
- Cooling test · Cooling
- Comfort circulating fan (FAN Prog) · Standby/shutdown
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: TCONT302 and 303 installation and user guide, p. 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.