Energy management recovery (early start)

XR302XR303TCONT302TCONT303

What happens, in order

  1. Thermostat compares the current room temperature with the next program setpoint.
  2. It starts heating early so the room reaches the setpoint at the programmed time.
  3. Cooling gets more lead time than heating because it takes longer to change temperature.

Timings and thresholds

ItemValue
Heating allowance5 minutes per degree F rise (example from manual)

Applies to: Programmable heat mode with EMR On

Models

TCONT302TCONT303

More Trane general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: TCONT302 and 303 installation and user guide, p. 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.