Trane · General · Cooling
Cooling test
What happens, in order
- Press the System button to select Cool.
- Set the thermostat 1 degree below room temperature.
- The blower should start on high speed right away, followed by cold air. Cool On shows.
- Set the thermostat 1 degree above room temperature. Cooling should stop and the Cool On icon clears.
Timings and thresholds
| Item | Value |
|---|---|
| Compressor lockout delay (item 50) | up to 5 minutes |
Codes you may see during this
Applies to: XR203 thermostat
Models
More Trane general sequences
- Energy management recovery (early start) · Heating
- Heating system test · Heating
- Heating test · Heating
- Compressor lockout delay · Cooling
- Compressor optimization fan delay · Cooling
- Cool Savings temperature offset · Cooling
- Cooling system test · Cooling
- Comfort circulating fan (FAN Prog) · Standby/shutdown
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR203 installation and user guide, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.