Compressor lockout delay

XR302XR303TCONT302TCONT303

What happens, in order

  1. With CL On, the thermostat waits between cooling cycles to protect the compressor.
  2. The setpoint flashes while the delay is active.
  3. Set CL to OFF if the compressor already has its own time delay built in. Ask the compressor maker.

Timings and thresholds

ItemValue
Minimum off time between cool cycles5 minutes (default)

Applies to: Screen 12 compressor lockout

Models

TCONT302TCONT303

More Trane general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: TCONT302 and 303 installation and user guide, p. 14, 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.