Trane · General · Standby/shutdown
Comfort circulating fan (FAN Prog)
What happens, in order
- Press FAN until FAN Prog shows.
- Fan cycles on for 10 minutes and off for 20 minutes when there has been no heat or cool call in the past 60 minutes.
Timings and thresholds
| Item | Value |
|---|---|
| Fan on | 10 minutes |
| Fan off | 20 minutes |
| No-call window before cycling starts | 60 minutes |
Applies to: Fan Prog setting
Models
More Trane general sequences
- Energy management recovery (early start) · Heating
- Heating system test · Heating
- Heating test · Heating
- Compressor lockout delay · Cooling
- Compressor optimization fan delay · Cooling
- Cool Savings temperature offset · Cooling
- Cooling system test · Cooling
- Cooling test · Cooling
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR302/XR303 installation and user guide, p. 19-20. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.