Trane · General · Cooling

Cooling system test

XR202TCONT202

What happens, in order

  1. Confirm outdoor temperature is at least 55°F. Do not run cooling below 55°F.
  2. Confirm the compressor oil heaters have been on for 6 hours and the system has been off for at least 5 minutes.
  3. Move the System Switch to Cool.
  4. Set the thermostat 1 degree below room temperature. The blower should start on high speed, followed by cool air. The display should show Cool On.
  5. Set the thermostat 1 degree above room temperature. Cooling should stop and the display should show Cool.

Timings and thresholds

ItemValue
Compressor start delay with lockout OnUp to 5 minutes
Compressor oil heater warm-up before cooling6 hours
Minimum system off time before compressor run5 minutes

Codes you may see during this

Cool On Cool Starting Soon

Applies to: Cool mode test

More Trane general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD51D1-1C-EN Installation and User Guide, p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.