Trane · General · Cooling
Cool Savings temperature offset
What happens, in order
- Cool Savings is active only when the air conditioner runs longer than 20 minutes.
- The displayed indoor temperature is offset downward, up to the amount set on screen 21.
- When the peak load drops, the offset returns to zero and the setpoint takes over again.
- Cool Savings flashes on the display while an offset is active.
Timings and thresholds
| Item | Value |
|---|---|
| First 1 degree offset | 1 hour of continuous AC run time |
| Each additional 1 degree | every 1/2 hour more run time |
Applies to: Screen 20 and 21 set On
Models
More Trane general sequences
- Energy management recovery (early start) · Heating
- Heating system test · Heating
- Heating test · Heating
- Compressor lockout delay · Cooling
- Compressor optimization fan delay · Cooling
- Cooling system test · Cooling
- Cooling test · Cooling
- Comfort circulating fan (FAN Prog) · Standby/shutdown
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: TCONT302 and 303 installation and user guide, p. 16. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.