Trane · General · Other

Fan operation test

XR202TCONT202

What happens, in order

  1. Turn on power to the system.
  2. If the system has no G terminal connection, skip this test.
  3. Press the fan button to select On. The blower should start.
  4. Press the fan button to select Auto. The blower should stop immediately.

Timings and thresholds

ItemValue
Blower response after switching to AutoStops immediately

Applies to: Systems with a G terminal connection

More Trane general sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 18-HD51D1-1C-EN Installation and User Guide, p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.