Trane · Heat pump · Cooling

Cooling sequence

XR103TCONT103

What happens, in order

  1. Set the SYSTEM switch to COOL.
  2. Set the setpoint below room temperature. The blower starts on high speed, then cold air is delivered.
  3. Set the setpoint above room temperature. Cooling stops.

Timings and thresholds

ItemValue
Compressor oil heater run before compressor use6 hours
System off before compressor restartat least 5 minutes
Minimum outdoor temperature for cooling55°F (do not run cooling below this)

Applies to: Heat pump cooling

Models

TCONT103XR103

More Trane heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane TCONT103 installation and user guide, p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.