Trane · Heat pump · Cooling
Cooling sequence
What happens, in order
- Set the SYSTEM switch to COOL.
- Set the setpoint below room temperature. The blower starts on high speed, then cold air is delivered.
- Set the setpoint above room temperature. Cooling stops.
Timings and thresholds
| Item | Value |
|---|---|
| Compressor oil heater run before compressor use | 6 hours |
| System off before compressor restart | at least 5 minutes |
| Minimum outdoor temperature for cooling | 55°F (do not run cooling below this) |
Applies to: Heat pump cooling
Models
More Trane heat pump sequences
- Fan check · Startup
- Dual fuel transition from furnace to heat pump · Heating
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence · Heating
- Heat pump heating sequence and aux stage · Heating
- Heat pump low-temperature fallback to aux · Heating
- Heat pump warm air discharge · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane TCONT103 installation and user guide, p. 9. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.