Aggressive recovery after a large setpoint change

XR402

What happens, in order

  1. A setpoint change that creates a temperature error of 2 degrees or more triggers aggressive recovery.
  2. The normal delay between compressor stages is skipped.
  3. The normal delay between the highest compressor stage and the first auxiliary heat stage is also skipped.
  4. Installer step 35 applies to both heating and cooling and overrides step 45 when enabled.

Timings and thresholds

ItemValue
Normal delay between compressor stages10 minutes
Setpoint change that triggers recovery2 degrees or more

Applies to: Systems with aggressive recovery enabled

More Trane heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.