Aggressive recovery after a large setpoint change
What happens, in order
- A setpoint change that creates a temperature error of 2 degrees or more triggers aggressive recovery.
- The normal delay between compressor stages is skipped.
- The normal delay between the highest compressor stage and the first auxiliary heat stage is also skipped.
- Installer step 35 applies to both heating and cooling and overrides step 45 when enabled.
Timings and thresholds
| Item | Value |
|---|---|
| Normal delay between compressor stages | 10 minutes |
| Setpoint change that triggers recovery | 2 degrees or more |
Applies to: Systems with aggressive recovery enabled
More Trane heat pump sequences
- Fan check · Startup
- Dual fuel transition from furnace to heat pump · Heating
- Emergency heat (EM) sequence, heat pump only · Heating
- Emergency heat sequence · Heating
- Heat pump heating sequence · Heating
- Heat pump heating sequence and aux stage · Heating
- Heat pump low-temperature fallback to aux · Heating
- Heat pump warm air discharge · Heating
Related
Trane error codes · Trane tips · Trane parts · All Trane sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Trane XR402 installer's guide 18-HD29D3-4, p. 15. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.