Rinnai · Boiler · Startup
Fill and deaerate the boiler during commissioning
What happens, in order
- Confirm all boiler components are installed correctly.
- Open the air vent inside the boiler.
- Confirm all heat emitters and pumps are connected to the piping.
- Power on the boiler. The fan runs for a safety check.
- Open the fill valve and fill the boiler to 20-30 PSI (138-207 kPa).
- Check the heating system for leaks.
- Start deaeration (press and hold SW2 on the PC board).
- Let deaeration run until the display shows End.
- Press the top left black button on the PC board to return to normal operation.
- Run DHW or CH to confirm normal operation.
- Close the air vent on the pump. Air should be removed through the air separator within about a week.
Timings and thresholds
| Item | Value |
|---|---|
| Deaeration run time | About 15 minutes, until the display shows End |
| Air removal from system | Up to one week |
Codes you may see during this
Applies to: I-Series Plus IP060160C
More Rinnai boiler sequences
- First-time settings from the boiler controller · Startup
- Normal ignition sequence · Startup
- DHW recirculation on a dedicated return line (flow check) · Domestic hot water
- DHW recirculation pump run logic (dedicated return mode) · Domestic hot water
- DHW recirculation with crossover valve and thermal bypass · Domestic hot water
- DHW run limit and heating restart · Domestic hot water
- Automated descaling flush sequence · Pump/purge
- Freeze protection operation · Freeze protection
Related
Rinnai error codes · Rinnai tips · Rinnai parts · All Rinnai sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 68-69. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.