Rinnai · Boiler · Pump/purge

Automated descaling flush sequence

I-Series Plus

What happens, in order

  1. Shut off gas and turn off the DHW and CH buttons.
  2. Remove the front panel and locate the PC board.
  3. Press SW3 on the PC board to enter descaling mode.
  4. Press the up or down arrow to select dES, then press Select.
  5. Set up valves and hoses, run the pump and circulate cleaner through the boiler.
  6. Press the CH button to start the countdown. The display shows 60 minutes remaining.
  7. After 60 minutes the display shows rnS and a beep sounds. Turn off the pump.
  8. Rinse cleaner from the system drain through hose H2 with autofill open to at least 20 PSI, close boiler valves 1 and 2 and shutoff V3, open drain valve V4 for five minutes, then close V4 and reopen V3 and boiler valves 1 and 2.
  9. Rinse cleaner from the boiler drain through hose H1, close V4, open boiler valves 1 and 2, close V3 for five minutes, then reopen V3.
  10. Press Select so the display shows End. Disconnect all hoses.
  11. Press Select to return to dES, then press SW3 to return to normal mode. Replace the front panel and restore gas.

Timings and thresholds

ItemValue
Cleaner circulation before countdownat least 1 hour at 4 gallons per minute (15.1 liters per minute)
Countdown display60 minutes, decreasing 1 per minute
System rinse per side5 minutes
Autofill pressure during flush and rinseat least 20 PSI

Codes you may see during this

dES 60 rnS End

Applies to: All I-Series Plus condensing combi boilers

More Rinnai boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 126, p. 127. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.