Rinnai · Boiler · Pump/purge
Automated descaling flush sequence
What happens, in order
- Shut off gas and turn off the DHW and CH buttons.
- Remove the front panel and locate the PC board.
- Press SW3 on the PC board to enter descaling mode.
- Press the up or down arrow to select dES, then press Select.
- Set up valves and hoses, run the pump and circulate cleaner through the boiler.
- Press the CH button to start the countdown. The display shows 60 minutes remaining.
- After 60 minutes the display shows rnS and a beep sounds. Turn off the pump.
- Rinse cleaner from the system drain through hose H2 with autofill open to at least 20 PSI, close boiler valves 1 and 2 and shutoff V3, open drain valve V4 for five minutes, then close V4 and reopen V3 and boiler valves 1 and 2.
- Rinse cleaner from the boiler drain through hose H1, close V4, open boiler valves 1 and 2, close V3 for five minutes, then reopen V3.
- Press Select so the display shows End. Disconnect all hoses.
- Press Select to return to dES, then press SW3 to return to normal mode. Replace the front panel and restore gas.
Timings and thresholds
| Item | Value |
|---|---|
| Cleaner circulation before countdown | at least 1 hour at 4 gallons per minute (15.1 liters per minute) |
| Countdown display | 60 minutes, decreasing 1 per minute |
| System rinse per side | 5 minutes |
| Autofill pressure during flush and rinse | at least 20 PSI |
Codes you may see during this
Applies to: All I-Series Plus condensing combi boilers
More Rinnai boiler sequences
- Fill and deaerate the boiler during commissioning · Startup
- First-time settings from the boiler controller · Startup
- Normal ignition sequence · Startup
- DHW recirculation on a dedicated return line (flow check) · Domestic hot water
- DHW recirculation pump run logic (dedicated return mode) · Domestic hot water
- DHW recirculation with crossover valve and thermal bypass · Domestic hot water
- DHW run limit and heating restart · Domestic hot water
- Freeze protection operation · Freeze protection
Related
Rinnai error codes · Rinnai tips · Rinnai parts · All Rinnai sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 126, p. 127. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.