Rinnai · Boiler · Domestic hot water
DHW recirculation pump run logic (dedicated return mode)
What happens, in order
- Pump turns on and runs until the DHW return water is within about 6°F (14°C) of the DHW setpoint, or until the run time limit is reached, whichever comes first.
- Pump stays off for the interval set by the DHW setpoint (see the DHW recirculation off-interval setting).
- When the boiler senses the crossover valve is closed, the pump turns off.
- After the off interval timer has passed, the pump turns on again.
- Power to the pump is cut at the T/T4 terminal on the PC board when the return reaches the cut-off point.
- If the pump flow drops below the minimum or the boiler sees no flow on a run, the boiler shows E631.
- Use an external timer (optional) to limit the pump schedule if needed.
Timings and thresholds
| Item | Value |
|---|---|
| Maximum pump run time per cycle | 20 minutes |
| Return water cut-off below DHW setpoint | about 6°F (14°C) |
| Minimum flow rate for boiler operation | 0.5 GPM (2 L/min) |
| Target DHW recirculation flow range | 1.3 to 4 GPM (5 to 15 L/min) |
| Maximum pump current on DHW_Pump / T/T4 connection | 2 Amps |
Codes you may see during this
E631
Applies to: I-Series Plus Condensing Combi Boiler, dedicated hot water return line
Models
More Rinnai boiler sequences
- Fill and deaerate the boiler during commissioning · Startup
- First-time settings from the boiler controller · Startup
- Normal ignition sequence · Startup
- DHW recirculation on a dedicated return line (flow check) · Domestic hot water
- DHW recirculation with crossover valve and thermal bypass · Domestic hot water
- DHW run limit and heating restart · Domestic hot water
- Automated descaling flush sequence · Pump/purge
- Freeze protection operation · Freeze protection
Related
Rinnai error codes · Rinnai tips · Rinnai parts · All Rinnai sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 104. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.