Rinnai · Boiler · Domestic hot water

DHW recirculation pump run logic (dedicated return mode)

I-Series Plus

What happens, in order

  1. Pump turns on and runs until the DHW return water is within about 6°F (14°C) of the DHW setpoint, or until the run time limit is reached, whichever comes first.
  2. Pump stays off for the interval set by the DHW setpoint (see the DHW recirculation off-interval setting).
  3. When the boiler senses the crossover valve is closed, the pump turns off.
  4. After the off interval timer has passed, the pump turns on again.
  5. Power to the pump is cut at the T/T4 terminal on the PC board when the return reaches the cut-off point.
  6. If the pump flow drops below the minimum or the boiler sees no flow on a run, the boiler shows E631.
  7. Use an external timer (optional) to limit the pump schedule if needed.

Timings and thresholds

ItemValue
Maximum pump run time per cycle20 minutes
Return water cut-off below DHW setpointabout 6°F (14°C)
Minimum flow rate for boiler operation0.5 GPM (2 L/min)
Target DHW recirculation flow range1.3 to 4 GPM (5 to 15 L/min)
Maximum pump current on DHW_Pump / T/T4 connection2 Amps

Codes you may see during this

E631

Applies to: I-Series Plus Condensing Combi Boiler, dedicated hot water return line

Models

IP120199CNIP150199CN

More Rinnai boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 104. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.