Rinnai · Boiler · Domestic hot water
DHW recirculation on a dedicated return line (flow check)
What happens, in order
- Confirm the plumbing has a dedicated hot water return line and a recirculation pump on the T/T4 terminal.
- Check that the pump flow stays between 0.8 and 4 GPM during runs; below 0.8 GPM the boiler shows E631.
- If flow drops under 0.4 GPM the pump stops and the boiler shows E631.
- Check the pump size against the pressure drop of the recirculation loop; maximum pump current is 2 Amps.
- Confirm the recirculation pump wiring and the optional timer are connected as shown.
Timings and thresholds
| Item | Value |
|---|---|
| Flow below which E631 appears | 0.8 GPM (3 L/min) |
| Flow below which pump stops | 0.4 GPM (1.5 L/min) |
Codes you may see during this
E631
Applies to: I-Series Plus Condensing Combi Boiler, dedicated return recirculation
Models
More Rinnai boiler sequences
- Fill and deaerate the boiler during commissioning · Startup
- First-time settings from the boiler controller · Startup
- Normal ignition sequence · Startup
- DHW recirculation pump run logic (dedicated return mode) · Domestic hot water
- DHW recirculation with crossover valve and thermal bypass · Domestic hot water
- DHW run limit and heating restart · Domestic hot water
- Automated descaling flush sequence · Pump/purge
- Freeze protection operation · Freeze protection
Related
Rinnai error codes · Rinnai tips · Rinnai parts · All Rinnai sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 101. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.