Rinnai · Boiler · Domestic hot water

DHW recirculation on a dedicated return line (flow check)

I-Series Plus

What happens, in order

  1. Confirm the plumbing has a dedicated hot water return line and a recirculation pump on the T/T4 terminal.
  2. Check that the pump flow stays between 0.8 and 4 GPM during runs; below 0.8 GPM the boiler shows E631.
  3. If flow drops under 0.4 GPM the pump stops and the boiler shows E631.
  4. Check the pump size against the pressure drop of the recirculation loop; maximum pump current is 2 Amps.
  5. Confirm the recirculation pump wiring and the optional timer are connected as shown.

Timings and thresholds

ItemValue
Flow below which E631 appears0.8 GPM (3 L/min)
Flow below which pump stops0.4 GPM (1.5 L/min)

Codes you may see during this

E631

Applies to: I-Series Plus Condensing Combi Boiler, dedicated return recirculation

Models

IP120199CNIP150199CN

More Rinnai boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 101. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.