Rinnai · Boiler

E430 Low water pressure in the heating system

High severity I-Series Plus

What the control is telling you

Shown until the boiler senses at least 13 PSI (90 kPa). Below 7.3 PSI the boiler will not operate. Between 7.3 and 13 PSI operation is limited. Raise the system pressure to clear it.

Applies to: I-Series Plus IP060160C condensing combi boiler

Likely causes

  • Heating system water pressure is too low
  • Air in the system or water lost through leaks
  • Pressure dropped during the first week after filling as air was purged

Test and repair steps

  1. Check the pressure on the controller or the pressure gauge.
  2. Fill the system until the pressure is between 20 and 30 PSI (138 to 207 kPa).
  3. Check the heating system for leaks and repair any found.
  4. Make sure the pressure stays at 13 PSI or higher so the code clears.
  5. If pressure keeps dropping, run deaeration to purge air from the system.

Other codes on the same units

  • 661 By-Pass (Combi Only)
  • 670 3-Way Valves (Combi Only)
  • 681 Hot Water Supply Temperature Abnormality (Combi Only)
  • E393 Outdoor sensor harness disconnected
  • End Descaling complete
  • FH Forced High Fire Mode
  • FL Forced Low Fire Mode
  • LC Lime scale detected on DHW side

Sequence of operation

What the unit does around this code, step by step.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 68-69, 73. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.