Rinnai · Boiler

661 By-Pass (Combi Only)

Medium severity I-Series Plus

What the control is telling you

Bypass servo valve fault.

Applies to: I-Series Plus combi boiler

Likely causes

  • Bypass servo resistance or voltage out of range
  • Harness or connector wet
  • PC board voltage abnormal
  • Bypass servo valve faulty

Test and repair steps

  1. Measure the resistance values and voltage of the bypass servo valve (see Electrical Diagnostics).
  2. Make sure the harness and connector are not wet.
  3. If PC board voltage is abnormal, replace the PC board.
  4. Otherwise, replace the bypass servo valve.

Other codes on the same units

  • 321 Outgoing Thermistor (Combi Only)
  • 331 Heat Exchanger Thermistor (Combi Only)
  • 341 Inlet Thermistor (Combi Only)
  • 631 DHW Recirculation Pump (Combi Only)
  • 651 Water Flow Control (Combi Only)
  • 670 3-Way Valves (Combi Only)
  • 681 Hot Water Supply Temperature Abnormality (Combi Only)
  • E393 Outdoor sensor harness disconnected

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 116. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.