681 Hot Water Supply Temperature Abnormality (Combi Only)
What the control is telling you
DHW temperature is above set point, usually because the bypass servo does not close.
Applies to: I-Series Plus combi boiler
Likely causes
- Bypass servo failed to close
- Bypass flow control faulty
- Inlet or heat exchanger thermistor wiring damaged
- Sensor resistance out of range
- Scale buildup on sensor
Test and repair steps
- Measure resistance and voltage of the bypass flow control (see Electrical Diagnostics).
- Replace the bypass flow control device if needed.
- Otherwise, check the inlet thermistor and heat exchanger thermistor wiring for damage.
- Measure the resistance of the sensor and replace if needed.
- Clean any scale buildup from the sensor.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 116. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.