Rinnai · Boiler
631 DHW Recirculation Pump (Combi Only)
What the control is telling you
DHW recirculation pump fault.
Applies to: I-Series Plus combi boiler
Likely causes
- Recirculation type does not match parameter 12
- Dedicated return line not installed properly
- Dirty inlet water filter or bypass filter
- Pump not connected to DHW pump terminal
- Pump undersized for the piping
- Air in the recirculation line
Test and repair steps
- Confirm the DHW recirculation setting matches parameter 12.
- Confirm the dedicated return line is installed properly.
- Clean the inlet water filter and bypass filter.
- Confirm the recirculation pump is connected to the DHW pump terminal.
- Confirm the pump is sized for the piping (should be higher than 1.3 GPM).
- Remove air from the recirculation line.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 115. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.