Rinnai · Boiler
E393 Outdoor sensor harness disconnected
What the control is telling you
Shows when Parameter 00 is set to A (default) and the wire harness to the outdoor temperature sensor is unplugged. While E393 is shown, the boiler runs at the central heating setpoint instead of outdoor reset.
Applies to: I-Series Plus Condensing Combi Boiler
Likely causes
- Outdoor sensor wire harness disconnected from the PC board
- Parameter 00 set to A while no outdoor sensor is connected
Test and repair steps
- Remove the front panel (two screws) to reach the PC board at the lower left.
- Reconnect the outdoor sensor harness to the outdoor sensor terminals.
- Confirm Parameter 00 is set to A so outdoor reset is active.
- Check the sensor wiring (minimum 18 AWG) for damage or loose connections.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 98. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.