Rinnai · Boiler

LC Lime scale detected on DHW side

Medium severity I-Series Plus

What the control is telling you

Shown when the lime condition check (parameter 16) finds lime scale on the DHW side of the plate heat exchanger. Clears once the plate heat exchanger has been flushed.

Applies to: I-Series Plus condensing combi boiler with lime condition check enabled

Likely causes

  • Lime scale build-up on the DHW side of the plate heat exchanger

Test and repair steps

  1. Flush the plate heat exchanger to remove the lime scale.
  2. Confirm the LC code clears from the display after flushing.
  3. If needed, turn the lime check off in parameter 16 only after confirming the water conditions.

Other codes on the same units

  • 681 Hot Water Supply Temperature Abnormality (Combi Only)
  • E393 Outdoor sensor harness disconnected
  • E430 Low water pressure in the heating system
  • End Descaling complete
  • FH Forced High Fire Mode
  • FL Forced Low Fire Mode
  • dES Descaling (automated flush) mode
  • rnS Rinsing stage (descaling flush)

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 91-92. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.