Rinnai · Boiler

Ignition safety test Test ionization lockout

Menu / mode display E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the display is showing

Unplug the ionization cable, start in SERV function 1; expect one start attempt and four retries, then lockout with E02 flashing. Reconnect and reset.

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Other codes on the same units

  • FILL Water pressure low / system empty
  • FUSE 24 V fuse defective
  • Good Good state (normal)
  • Green button reset Restore factory parameters
  • HIGH Water pressure too high
  • INFO Information chapter
  • P XX Water pressure read-out
  • PARA Parameter chapter

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.61. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.