Rinnai · Boiler

FUSE 24 V fuse defective

High severity E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the control is telling you

The fuse on the controller board is blown (or the transformer cable is not connected).

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

Likely causes

  • Blown fuse on controller PCB
  • Transformer cable not plugged in

Test and repair steps

  1. Check the transformer cable is connected.
  2. Replace the fuse. A 4 A and a 5 A spare are kept on the back of the Control Tower.
  3. If it blows again, look for a short on the 24 V side.

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.71-76 (15.1, 15.3). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.