Rinnai · Boiler
FILL Water pressure low / system empty
What the display is showing
Shown when the system is empty or pressure is below 10 PSI; the boiler stays out of service until topped up. Flashing FILL alternating with the pressure value (below 12 PSI) means reduced 50% power operation is possible.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
What to do
- Fill to 16-18 PSI cold
- Press STEP briefly to show P XX (pressure)
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.50-54 (8, 9.2). Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.