Rinnai · Boiler

PARA Parameter chapter

Menu / mode display E-Combi (E50CRNE75CRN/E75CRPE110CRN/E110CRP)

What the display is showing

Installer chapter for changing parameters (list in settings).

Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP

What to do

  1. Enter C123, press MODE until PARA
  2. STEP selects parameter, + / - changes, STORE confirms
  3. MODE until StBY/Good to leave; auto-exit after 20 min idle

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.56-58. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.