Rinnai · Boiler
SERV Service chapter
What the display is showing
Test functions: 1 burner on (max power), 2 fan, 3 pump, 4 showroom mode. Used for O2 check, ionization test and ignition safety test.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
What to do
- Enter C123, MODE until SERV, STEP to function 1
- Use + to raise load, hold - to reach OFF/end the test
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.58, 61-63. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.