HTP · Boiler · Standby/shutdown

Standby and over-temperature protection

Elite EL

What happens, in order

  1. With no call the burner is off and the control waits
  2. 0-10 V below 1 V keeps the boiler in standby
  3. Flue above 210 F no burner, pump off until flue under 194 F (E07)
  4. Supply or return at 210 F or higher message, pump on, clears below 194 F
  5. Supply or return above 230 F lockout, pump on
  6. Water ECO trip F00 lockout, pump on
  7. Low water pressure no firing, pump off until restored

Timings and thresholds

ItemValue
E07 trip / clear210 F / 194 F
F05 and F06 message / clear210 F / 194 F
F05 and F06 lockoutAbove 230 F
Min system pressure10 psig

Codes you may see during this

E07 F00 F01 F05 F06 PRO

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More HTP boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 65, p. 67, p. 68, p. 69, p. 70. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.