HTP · Boiler · Heating

Outdoor reset and warm weather shutoff

Elite EL

What happens, in order

  1. Outdoor sensor reads outside temperature
  2. Control sets the heating set point from the curve between min and max outdoor/supply points
  3. Lowering the CH set point shifts the curve down
  4. If the outdoor temperature exceeds the warm weather setting the boiler is disabled
  5. If the outdoor sensor fails (and function 21 is on) the control ignores reset and uses the programmed temperature

Timings and thresholds

ItemValue
Warm weather shutoff68 F default
Min outdoor / max supply5 F / 190 F default
Max outdoor / min supply68 F / 95 F default

Codes you may see during this

FOU

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More HTP boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 55, p. 56, p. 60, p. 67. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.