HTP · Boiler · Pump/purge

Pump service mode

Elite EL

What happens, in order

  1. Remove call for heat
  2. Press down arrow and ENTER together for 1 second
  3. CH pump runs
  4. Next press steps to the DHW pump, then the system pump on a cascade master
  5. Down and up arrows together return to normal

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More HTP boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 50. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.