HTP · Boiler · Domestic hot water

Indirect water heater call

Elite EL

What happens, in order

  1. DHW sensor (or aquastat) calls when tank temperature drops below DHW set point by more than the offset
  2. DHW pump on
  3. Boiler runs at the boiler DHW supply temperature
  4. Control checks supply temperature against DHW set point minus differential and shows TEMPER BLOCKING if too hot
  5. Demand continues until tank is above set point
  6. DHW pump can run on for the DHW post pump time
  7. DHW priority limits DHW run time and guarantees a minimum central heat run time

Timings and thresholds

ItemValue
DHW set point119 F default
DHW differential7 F default
Boiler supply for DHW180 F default
DHW post pump0 min default (0 to 10)
DHW priority30 min default (0 to 60)

Codes you may see during this

DHW

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More HTP boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 43, p. 56, p. 57. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.