HTP · Boiler
DHW Temperature blocking - DHW demand
What the display is showing
Indirect tank call is present and the pump runs, but supply water is too hot for the boiler to ignite.
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Good to know
- Supply sensor reads higher than DHW set point minus DHW differential when the DHW call arrives.
What to do
- Compare the SUPPLY reading with DHW set point minus the DHW differential
- Wait until the supply water drops below that value; the message clears by itself
Models that show this code
12 models in Elite EL
Other codes on the same units
- F31 Program error
- CASCADE MASTER READY Cascade master ready
- CASCADE NO FOLLOWER Cascade - no follower
- CASCADE NO SENSOR Cascade - no system sensor
- FL Low water flow
- FLU High flue pressure
- FOU Outdoor sensor fault
- GAS VALVE ON / RUN Ignition then run status
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Elite EL-80 N Installation Manual (LP-293), p. 66, p. 67. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.