HTP · Boiler
FLU High flue pressure
What the control is telling you
Flue pressure switch shows excessive pressure; pump on. Resets automatically when the pressure is gone.
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Likely causes
- Blocked flue or vent
- Flue pressure switch or its wiring faulty
Test and repair steps
- Make sure the flue is not blocked
- Jumper the switch to test the wiring; if the code clears, replace the switch and wire the new one in before running the boiler
- Never leave a jumper in place - a bad switch must be replaced
Models that show this code
12 models in Elite EL
Other codes on the same units
- CASCADE NO FOLLOWER Cascade - no follower
- CASCADE NO SENSOR Cascade - no system sensor
- DHW Temperature blocking - DHW demand
- FL Low water flow
- FOU Outdoor sensor fault
- GAS VALVE ON / RUN Ignition then run status
- LOCKOUT Lockout (display message)
- LOU 24 volt supply low
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Elite EL-80 N Installation Manual (LP-293), p. 67, p. 68. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.