HTP · Boiler

LOU 24 volt supply low

Medium severity Elite EL

What the control is telling you

Control's 24 V supply is damaged or overloaded; pump on. Clears itself if the overload goes away.

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

Likely causes

  • Line voltage out of range
  • Shorted external sensor wiring
  • Short in the low voltage harness
  • Optional UL353 low water cut-off loading the supply
  • Gas valve drawing too much current at light-off
  • Failed control board

Test and repair steps

  1. Check line voltage is between 100 and 128 V
  2. If available, connect a PC with the service software and check the 24 V reading: it should be above 128 and no more than 250
  3. Unplug the 10-pin Molex from the customer connection board: if the message clears, look for shorts to ground in the external sensor wiring
  4. If still present, disconnect the UL353 low water cut-off to see if it clears
  5. Check the low voltage harness for shorts to ground
  6. If it only appears when the burner tries to light, check the gas valve current draw
  7. If it remains with the low voltage harness unplugged from the board, replace the control board

Models that show this code

12 models in Elite EL

EL-110 LPEL-110 NEL-150 LPEL-150 NEL-220 LPEL-220 NEL-299 LPEL-299 NEL-399 LPEL-399 NEL-80 LPEL-80 N

Other codes on the same units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 68. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.