FOU Outdoor sensor fault
What the control is telling you
Outdoor sensor is shorted, open, or the outdoor temperature is below -40 F. Boiler keeps running and ignores outdoor reset, using the programmed boiler temperature.
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Likely causes
- Outdoor sensor wiring damaged or shorted
- Sensor defective
Test and repair steps
- Inspect the outdoor sensor wiring for damage or shorts and repair
- Measure the sensor resistance and compare with the chart; replace if out of range
Models that show this code
12 models in Elite EL
Other codes on the same units
- CASCADE NO SENSOR Cascade - no system sensor
- DHW Temperature blocking - DHW demand
- FL Low water flow
- FLU High flue pressure
- GAS VALVE ON / RUN Ignition then run status
- LOCKOUT Lockout (display message)
- LOU 24 volt supply low
- MAINTENANCE REQUIRED Service reminder
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Elite EL-80 N Installation Manual (LP-293), p. 67. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.