HTP · Boiler
PRO Low water pressure
What the control is telling you
System water pressure is too low for the boiler to run; pump off. Resets automatically once pressure is restored.
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Likely causes
- System pressure below the minimum
- Leak in the system piping
Test and repair steps
- Confirm the system pressure is above 10 psig
- Look for leaks in the piping and refill to proper pressure
Models that show this code
12 models in Elite EL
Other codes on the same units
- GAS VALVE ON / RUN Ignition then run status
- LOCKOUT Lockout (display message)
- LOU 24 volt supply low
- MAINTENANCE REQUIRED Service reminder
- PP Control programmed
- SERVICE PUMP CH / DH / SH Pump service mode
- SERVICE RUN Test mode running
- TT Temperature blocking - thermostat (TT) demand
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Elite EL-80 N Installation Manual (LP-293), p. 68. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.