HTP · Boiler · Other

Cascade operation

Elite EL

What happens, in order

  1. Master sees a heat call from TT contact, DHW sensor or 0-10 V
  2. Master checks which follower addresses answer on the bus
  3. Master brings boilers up toward the cascade set point staged by demand
  4. Firing order rotates after the rotation time
  5. If the system sensor is missing, all boilers fire together
  6. System pump runs from the master dry contact

Timings and thresholds

ItemValue
Max boilers8 (address 0 to 7)
Rotation48 h default (0 to 240)
Max cascade set point190 F
Max bus cable length200 ft

Codes you may see during this

E03

Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)

More HTP boiler sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Elite EL-80 N Installation Manual (LP-293), p. 6, p. 63, p. 64, p. 58. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.