Goodman-Amana-Daikin sequences of operation
13 sequences for Goodman-Amana-Daikin equipment: what the unit does, step by step, with the timings. Pick the equipment type, then the mode.
Air conditioner (2)
Cooling
- Communicating low and high stage cooling
Goodman ComfortNet communicating (ASXC, GSXC, DSXC with AVPTC) - Cooling call with blower board delays
Goodman R-410A single/two-stage AC with MBR, AR*F
Air handler (1)
Other
- R-32 leak detection response and test
Goodman R-32 with RDS leak detection
Furnace (6)
Ignition
- Gas heat call and shutdown
GM9S80, GC9S80 single-stage 80 percent - Gas heat call, first and second stage
Two-stage 96 percent (integrated 7-segment control)
Heating
- Two-stage gas heat call with ramped blower
GMVC95, GMVC9 two-stage variable-speed
Cooling
- Cooling and fan only
GM9S80, GC9S80 single-stage 80 percent - Cooling and fan only
GMVC95, GMVC9 two-stage variable-speed - Low and second stage cooling with the furnace blower
Two-stage 96 percent (integrated 7-segment control)
Heat pump (4)
Heating
- Communicating heat pump heat, balance point and auxiliary heat
Goodman ComfortNet communicating heat pump (ASZC, GSZC, DSZC with AVPTC) - Heat pump heat with electric backup stages
Goodman R-410A heat pump with AEPF, MBR air handler
Defrost
- Communicating defrost and forced defrost
Goodman ComfortNet communicating heat pump - Timed defrost with sensor and override
Goodman R-410A and R-32 heat pump defrost board
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.