Goodman-Amana-Daikin · Heat pump · Defrost

Timed defrost with sensor and override

Goodman R-410A and R-32 heat pump defrost board

What happens, in order

  1. Heat pump runs in heating with the reversing valve de-energized
  2. Defrost board checks the outdoor coil sensor at the chosen interval of heat pump run time (30, 60 or 90 min)
  3. Timing starts when the sensor closes (about 31 F) and the thermostat calls for heat
  4. If the sensor is still closed at the end of the interval, defrost starts
  5. Outdoor fan relay opens (outdoor fan off)
  6. Reversing valve and electric heat are energized (24 V sent to O and W2)
  7. Defrost ends when the sensor opens (about 75 F)
  8. If the sensor never opens, the board ends defrost on a 10 minute override (12 minutes on the upgraded board)
  9. At the end the outdoor fan restarts and the reversing valve and electric heat de-energize; normal heating resumes
  10. Boards PCBDM133 / PCBDM160 factory DLY setting stops the compressor for 30 s while the valve shifts at the start and end of defrost; move the jumper to NORM to skip the delay

Timings and thresholds

ItemValue
Defrost check interval30, 60 or 90 min
Sensor closesabout 31 F
Sensor opens / defrost endsabout 75 F
Override10 min (12 min upgraded control)
Compressor delay on shift (DLY)30 s

Applies to: Goodman ASZ/GSZ/DSZ R-410A heat pumps (incl. GSZH5); Goodman R-32 GLZS / ALZS heat pumps

Models

ASZGSZDSZGSZH5GLZSALZS

More Goodman-Amana-Daikin heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman R-410A ASX/GSX/DSX A-C and ASZ/GSZ/DSZ HP service RS6200006, Defrost Operation; Goodman R-32 service RS6200301, Defrost Cycle. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.