Goodman-Amana-Daikin · Heat pump · Heating

Heat pump heat with electric backup stages

Goodman R-410A heat pump with AEPFMBR air handler

What happens, in order

  1. Thermostat set to heat reversing valve stays de-energized
  2. First stage call 24 V to Y at the outdoor unit and G at the blower board
  3. Heat pump starts; blower starts after the 7 s on delay
  4. If the heat pump cannot keep up, W2 energizes the heat sequencer HR1 and element 1 (and 2) come on 10 to 20 s later
  5. If still short, W3 energizes HR2 for elements 3 and 4
  6. When demand is met, elements drop out (sequencer contacts open 30 to 70 s after power is removed)
  7. Heat pump stops and the blower stops after the 65 s off delay

Timings and thresholds

ItemValue
Blower on delay7 s
Blower off delay65 s
Sequencer pull-in10 to 20 s
Sequencer drop-out30 to 70 s

Applies to: Goodman heat pumps matched with MBR / AR*F or MBE / AEPF air handlers (mercury bulb thermostat sequence)

Models

ASZGSZDSZ with MBR/AR*FMBE/AEPF

More Goodman-Amana-Daikin heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman R-410A ASX/GSX/DSX A-C and ASZ/GSZ/DSZ HP service RS6200006, Sequence of Operation sections 3.0 and 4.0. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.