Goodman-Amana-Daikin · Furnace · Cooling
Cooling and fan only
What happens, in order
- R and Y1/G or Y2/G close; control checks safeties
- Outdoor fan and compressor start at the right speed
- Circulator blower starts on the cool speed, level and timing set by the chosen ramp profile; air cleaner terminal energized
- Thermostat opens outdoor fan and compressor stop
- Blower keeps running through a cool off delay (time and airflow set by the ramp profile), then blower and air cleaner turn off
- Fan only R and G close; after a 5 s delay the blower runs at continuous fan speed (30 percent of furnace maximum airflow) with the air cleaner on; it stops when G opens
Timings and thresholds
| Item | Value |
|---|---|
| Fan-only start delay | 5 s |
| Continuous fan airflow | 30 percent of max |
Applies to: Goodman GMVC95 two-stage variable-speed furnaces
Models
More Goodman-Amana-Daikin furnace sequences
- Gas heat call and shutdown · Ignition
- Gas heat call, first and second stage · Ignition
- Two-stage gas heat call with ramped blower · Heating
- Cooling and fan only · Cooling
- Low and second stage cooling with the furnace blower · Cooling
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC950704CX (IO-341D), Normal Sequence of Operation - cooling and fan only. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.