Goodman-Amana-Daikin · Furnace · Cooling

Cooling and fan only

GMVC95GMVC9 two-stage variable-speed

What happens, in order

  1. R and Y1/G or Y2/G close; control checks safeties
  2. Outdoor fan and compressor start at the right speed
  3. Circulator blower starts on the cool speed, level and timing set by the chosen ramp profile; air cleaner terminal energized
  4. Thermostat opens outdoor fan and compressor stop
  5. Blower keeps running through a cool off delay (time and airflow set by the ramp profile), then blower and air cleaner turn off
  6. Fan only R and G close; after a 5 s delay the blower runs at continuous fan speed (30 percent of furnace maximum airflow) with the air cleaner on; it stops when G opens

Timings and thresholds

ItemValue
Fan-only start delay5 s
Continuous fan airflow30 percent of max

Applies to: Goodman GMVC95 two-stage variable-speed furnaces

Models

GMVC95GMVC9

More Goodman-Amana-Daikin furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC950704CX (IO-341D), Normal Sequence of Operation - cooling and fan only. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.