Goodman-Amana-Daikin · Air conditioner · Cooling

Cooling call with blower board delays

Goodman R-410A single/two-stage AC with MBRAR*F

What happens, in order

  1. Thermostat energizes G and Y; 24 V reaches Y at the condensing unit and G on the EBTDR blower board
  2. Compressor and condenser fan start
  3. 7 s later the EBTDR relay closes and the blower starts
  4. Thermostat satisfied G and Y drop
  5. Compressor and condenser fan stop; the blower stops after the 65 s delay-off

Timings and thresholds

ItemValue
Blower on delay7 s
Blower off delay65 s

Applies to: Goodman ASX / GSX / DSX air conditioners with MBR / AR*F air handlers

Models

ASXGSXDSX

More Goodman-Amana-Daikin air conditioner sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman R-410A ASX/GSX/DSX A-C and ASZ/GSZ/DSZ HP service RS6200006, Sequence of Operation 1.0. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.