Viessmann · Heat pump
PC02 Compressor top temperature or IPM high temperature / high pressure protection
What the control is telling you
Triggered when the compressor top temperature or IPM module temperature is too high, the sampling voltage is wrong, or the high pressure switch opens (above 4.4 MPa on some models).
Applies to: Outdoor compressor and IPM temperature and pressure protection
Likely causes
- Blocked indoor or outdoor airflow
- Refrigerant system fault or blockage
- Faulty overload protector (OLP)
- Loose connections
- Loose PCB or IPM radiator screws
- Faulty outdoor control PCB or IPM board
- Faulty high pressure protector
Test and repair steps
- Check the indoor and outdoor airflow for obstructions and clear the air inlets and outlets and heat exchangers.
- Turn off the power, wait 10 minutes and turn it back on.
- Check whether the compressor top temperature is above 90 °C.
- Check the refrigerant system and repair it if abnormal.
- Check all connections, especially the OLP connection; correct any faults.
- Measure resistance between the two OLP ports; if zero, replace the OLP.
- Check the PCB and IPM radiator fastening screws; tighten them and apply silicone grease if loose.
- Replace the outdoor control PCB if the fault remains.
Other codes on the same units
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- EL01 Indoor and outdoor unit communication error
- PC00 IPM malfunction or IGBT over-strong current protection
- PC01 Overvoltage or low voltage protection
- PC08 Current overload protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLFSHC Service Manual, p. 32. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.