Viessmann · Heat pump

PC03 Low pressure protection

High severity Vitocal 100-SDLCSRB

What the control is telling you

The outdoor pressure switch shuts the unit down when low pressure drops below 0.13 MPa.

Applies to: DLCSRB outdoor units, sizes 06 to 36

Likely causes

  • Loose or faulty low pressure protector wiring
  • Faulty low pressure protector
  • Outdoor ambient too low
  • Insufficient refrigerant
  • High pressure valve core not fully open
  • Indoor fan not running properly in cooling mode
  • Faulty outdoor main board

Test and repair steps

  1. Check that the low pressure protector and main control board are wired correctly. Reconnect them if needed.
  2. Disconnect the plug and measure the low pressure protector; a normal protector reads zero. Replace it if it is open.
  3. Check that the outdoor ambient temperature is not too low.
  4. Make sure the high pressure valve core is fully open.
  5. Check that the indoor fan runs properly in cooling mode. Refer to the fan speed section if it does not.
  6. If refrigerant is low, check the system for leaks and add refrigerant. Confirm the system works after adding it.
  7. If the fault remains, replace the outdoor main board.

Models that show this code

22 models in Vitocal 100-S, DLCSRB

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Other codes on the same units

  • PC0A High temperature protection of condenser
  • PC0F PFC module protection
  • PC0L Low temperature protection of outdoor unit
  • PC04 Inverter compressor drive error
  • PC06 Discharge temperature protection of compressor
  • PC10 Outdoor unit low AC voltage protection
  • PC11 Main control board DC bus high voltage protection
  • PC12 Main control board DC bus high voltage protection / 341 MCE error

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal 100-S DLCSRB service manual, p. 46. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.