Viessmann · Heat pump
PC04 Inverter compressor drive error
What the control is telling you
The special detection circuit found an abnormal inverter compressor drive. It checks communication, voltage, and compressor rotation and speed signals.
Applies to: DLCSRB outdoor units, sizes 06 to 36
Likely causes
- Improper wiring between the PCB and compressor
- Faulty IPM module board
- Outdoor fan or outdoor unit ventilation problem
- Faulty compressor
- Faulty outdoor PCB
Test and repair steps
- Check the wiring between the PCB and the compressor. Correct the connections or replace wires and connectors if needed.
- Check the IPM. If it is not working properly, replace the IPM board or the outdoor PCB.
- Check the outdoor fan and outdoor unit ventilation. If the fan is not working properly, see the fan speed malfunction section.
- Check the compressor resistance values. Replace the compressor if they are out of range.
- If the fault remains, replace the outdoor PCB.
Models that show this code
22 models in Vitocal 100-S, DLCSRB
Other codes on the same units
- PC0A High temperature protection of condenser
- PC0F PFC module protection
- PC0L Low temperature protection of outdoor unit
- PC03 Low pressure protection
- PC06 Discharge temperature protection of compressor
- PC10 Outdoor unit low AC voltage protection
- PC11 Main control board DC bus high voltage protection
- PC12 Main control board DC bus high voltage protection / 341 MCE error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal 100-S DLCSRB service manual, p. 45. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.