Viessmann · Heat pump
EL01 Indoor and outdoor unit communication error
What the control is telling you
The indoor unit cannot communicate with the outdoor unit.
Applies to: DLFSHC indoor and outdoor units, all sizes
Likely causes
- Indoor PCB fault
- Outdoor PCB fault
- Short-circuited component on the high voltage side (4-way valve, heater, AC fan)
- Bad wiring between indoor and outdoor units or between PCBs
- Electronic expansion valve coil fault
Test and repair steps
- Power off, then restart the unit after two minutes. If the code disappears, stop.
- Check the wiring between the indoor and outdoor units. Correct or replace wires if needed.
- Check the wiring from the outdoor terminal to the outdoor PCB and between PCBs if there is more than one PCB.
- Check the wiring from the indoor terminal to the indoor PCB.
- Turn the unit on and check that W and 1(L) are connected. Check that the power LED is on.
- Measure the DC voltage between N/L2 and S (red to N/L2, black to S). A fluctuating value from negative to positive is correct. A fixed value near 0 or always positive points to a fault.
- Unplug the high voltage components on the main PCB (4-way valve, heater, AC fan) one at a time and check their resistance. Replace any short-circuited component and the main PCB.
- Unplug the electronic expansion valve and check whether the power LED and the 5V and 12V DC supplies are correct. Replace the expansion valve coil if needed.
- On units with a separate IPM board, check the AC voltage of L and N to the IPM board against the power input. Check the 5V and 12V DC from the IPM board to the main PCB. Replace the IPM board if faulty.
- Replace the indoor or outdoor PCB as the flowchart shows. On some models the whole outdoor electric control box must be replaced.
Other codes on the same units
- EH02 Zero crossing detection error
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- PC00 IPM malfunction or IGBT over-strong current protection
- PC01 Overvoltage or low voltage protection
- PC02 Compressor top temperature or IPM high temperature / high pressure protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.