Viessmann · Heat pump

EL01 Indoor and outdoor unit communication error

High severity DLFSHC

What the control is telling you

The indoor unit cannot communicate with the outdoor unit.

Applies to: DLFSHC indoor and outdoor units, all sizes

Likely causes

  • Indoor PCB fault
  • Outdoor PCB fault
  • Short-circuited component on the high voltage side (4-way valve, heater, AC fan)
  • Bad wiring between indoor and outdoor units or between PCBs
  • Electronic expansion valve coil fault

Test and repair steps

  1. Power off, then restart the unit after two minutes. If the code disappears, stop.
  2. Check the wiring between the indoor and outdoor units. Correct or replace wires if needed.
  3. Check the wiring from the outdoor terminal to the outdoor PCB and between PCBs if there is more than one PCB.
  4. Check the wiring from the indoor terminal to the indoor PCB.
  5. Turn the unit on and check that W and 1(L) are connected. Check that the power LED is on.
  6. Measure the DC voltage between N/L2 and S (red to N/L2, black to S). A fluctuating value from negative to positive is correct. A fixed value near 0 or always positive points to a fault.
  7. Unplug the high voltage components on the main PCB (4-way valve, heater, AC fan) one at a time and check their resistance. Replace any short-circuited component and the main PCB.
  8. Unplug the electronic expansion valve and check whether the power LED and the 5V and 12V DC supplies are correct. Replace the expansion valve coil if needed.
  9. On units with a separate IPM board, check the AC voltage of L and N to the IPM board against the power input. Check the 5V and 12V DC from the IPM board to the main PCB. Replace the IPM board if faulty.
  10. Replace the indoor or outdoor PCB as the flowchart shows. On some models the whole outdoor electric control box must be replaced.

Other codes on the same units

  • EH02 Zero crossing detection error
  • EH03 Indoor fan speed outside normal range
  • EH06 Indoor PCB and display board communication error
  • EH60 Indoor temperature sensor open or short circuit (T1, T2)
  • EL0C Refrigerant leakage detection
  • PC00 IPM malfunction or IGBT over-strong current protection
  • PC01 Overvoltage or low voltage protection
  • PC02 Compressor top temperature or IPM high temperature / high pressure protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 17. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.