Viessmann · Heat pump
EL0C Refrigerant leakage detection
What the control is telling you
In the first 5 minutes after compressor start, the evaporator coil temperature (T2) does not drop as expected while the compressor runs above 50 Hz. This happens three times and the unit shuts off.
Applies to: Indoor unit evaporator coil sensor T2 and refrigerant circuit
Likely causes
- Refrigerant leak or undercharge
- Blocked airflow or system blockage
- Faulty T2 sensor
- Faulty indoor PCB
Test and repair steps
- Power off the unit and restart it 2 minutes later.
- Check the system for blockages and clear any found.
- Place a hand at the indoor air outlet and check whether cool air is blowing.
- Check that the T2 sensor is securely attached and in working order.
- Check the system for leaks; if a leak is found, repair it and recharge the refrigerant.
- If no cool air and the sensor is fine, replace the indoor PCB.
Other codes on the same units
- EH02 Zero crossing detection error
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL01 Indoor and outdoor unit communication error
- PC00 IPM malfunction or IGBT over-strong current protection
- PC01 Overvoltage or low voltage protection
- PC02 Compressor top temperature or IPM high temperature / high pressure protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLFSHC Service Manual, p. 25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.