Viessmann · Heat pump

EH06 Indoor PCB and display board communication error

Medium severity DLFSHCVitocal IND-H

What the control is telling you

The indoor PCB is not receiving feedback from the display board.

Applies to: Indoor PCB to display board communication

Likely causes

  • Faulty communication wire
  • Faulty indoor PCB
  • Faulty display board
  • Loose connection

Test and repair steps

  1. Check the wiring and connections between the indoor PCB and display board.
  2. Make sure all connections are secure.
  3. Power off, wait 2 minutes, then restart the unit.
  4. If the error remains, replace the indoor main PCB.
  5. If the error still exists after that, replace the display board.

Other codes on the same units

  • EC53 Outdoor temperature sensor open or short circuit (T3, T4, TP, T2B, TH)
  • EH02 Zero crossing detection error
  • EH03 Indoor fan speed outside normal range
  • EH60 Indoor temperature sensor open or short circuit (T1, T2)
  • EL0C Refrigerant leakage detection
  • EL01 Indoor and outdoor unit communication error
  • PC00 IPM malfunction or IGBT over-strong current protection
  • PC01 Overvoltage or low voltage protection

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: DLFSHC Service Manual, p. 26. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.