EC53 Outdoor temperature sensor open or short circuit (T3, T4, TP, T2B, TH)
What the control is telling you
If the sampling voltage is below 0.06 V or above 4.94 V, the unit shows the failure code. On some models T3, T4 and TP are one combination sensor.
Applies to: DLFSHC outdoor unit sensors T3, T4, TP, T2B and TH. On some models the control box is replaced as a whole.
Likely causes
- Open or shorted sensor
- Bad connection between sensor and PCB
- Outdoor main PCB fault
Test and repair steps
- Check the connection between the temperature sensor and the PCB.
- Make sure the wiring is proper.
- Measure the sensor resistance and compare it with the reference value in Figure 20.
- If the sensor is out of range, replace the sensor.
- If the sensor is within acceptable range, replace the outdoor main PCB.
Other codes on the same units
- EC07 Outdoor fan speed outside normal range
- EC51 Outdoor EEPROM parameter error or compressor driven chip EEPROM parameter error
- EH02 Zero crossing detection error
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- EL01 Indoor and outdoor unit communication error
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.