EH03 Indoor fan speed outside normal range
What the control is telling you
The indoor fan speed stays too slow or too fast for a long time. The unit shows the failure code and turns off.
Applies to: DLFSHC indoor unit
Likely causes
- Fan motor fault
- Fan assembly binding
- Fan motor wiring fault
- Indoor main PCB fault
Test and repair steps
- Turn the power off, wait two minutes, then restart. If the code clears, the unit is normal.
- If it remains, shut off the power and rotate the fan by hand.
- If the fan does not turn easily, find and fix the cause.
- Check the fan motor wiring and make sure the connections are good.
- Measure the fan motor voltage from the PCB. If it is wrong, replace the indoor main PCB.
- If the voltage is correct, replace the fan motor.
Other codes on the same units
- EC51 Outdoor EEPROM parameter error or compressor driven chip EEPROM parameter error
- EC53 Outdoor temperature sensor open or short circuit (T3, T4, TP, T2B, TH)
- EH02 Zero crossing detection error
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- EL01 Indoor and outdoor unit communication error
- PC00 IPM malfunction or IGBT over-strong current protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Viessmann Vitocal IND-H DLFSHC service manual, p. 20. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.