Viessmann · Heat pump
PC00 IPM malfunction or IGBT over-strong current protection
What the control is telling you
The IPM sends an abnormal voltage signal to the compressor drive chip. The unit turns off and the code is displayed.
Applies to: Outdoor IPM module and compressor drive
Likely causes
- Faulty communication or compressor wires
- Faulty IPM module board
- Outdoor fan assembly fault
- Faulty compressor
- Faulty outdoor PCB
- Incorrectly installed IPM
Test and repair steps
- Discharge the electrolytic capacitors fully before working on the unit.
- Check that the IPM terminal resistance is uniform (IPM continuity check).
- Check the wiring between the PCB and the compressor; fix or replace wires and connectors.
- Check that the IPM is installed correctly, tighten the screws and apply silicone grease.
- Check the outdoor fan and the outdoor unit ventilation.
- Check the compressor winding resistance; if the values are not equal, replace the compressor.
- Replace the IPM board or the outdoor PCB if the fault remains.
Other codes on the same units
- EH03 Indoor fan speed outside normal range
- EH06 Indoor PCB and display board communication error
- EH60 Indoor temperature sensor open or short circuit (T1, T2)
- EL0C Refrigerant leakage detection
- EL01 Indoor and outdoor unit communication error
- PC01 Overvoltage or low voltage protection
- PC02 Compressor top temperature or IPM high temperature / high pressure protection
- PC08 Current overload protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: DLFSHC Service Manual, p. 28. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.